Industrial Dehumidifier TROTEC TT6600
Capacity 1000 lt/24h
Sheet steel casing, galvanized and powder coated
- Built-in G4 air filters as Z Line version, separate for process air and
regeneration air
- Filter monitoring with alarm indicator light
- Rotor rotation control
- Control voltage 24 V DC
- Potential-free contacts for filter maintenance/replacement, fault,
on/off operation
- Connection terminals for hygrostat, 24 V DC
- Connection terminals for external on/off, 24 V DC
- High-voltage direct-supply EC fans integrated in the casing,
with manual speed control (no need to employ
additional butterfly valves), separate for process air and the
regeneration
- Flowmatic S, separate electronic fan speed control
for regeneration and process air, volumetric flow control or
of constant pressure depending on the process-side setpoint, control signal
control 0...10 V and 4-20 mA
- Silicagel adsorption rotor with internal rinse sector for recovery
thermal and independently adaptable rotor seal set
- Rotor drive system with brushless gear motor with
speed adjustment, toothed belt, pulley and belt tensioner
- Electric regeneration air heater consisting of heating elements
tubular, equipped with safety temperature limiters and switch of
differential pressure, controlled by semiconductor relay
- Millenium microprocessor control with plain text display in
four lines
- Error notifications indicated with plain text display
- Energy management (adjustment of regeneration air heating according to
depending on the temperature)
- Adjustment of dry air humidity (only in connection with optional
optional humidity meter and the 4-20 mA / 0-10 V transducer kit)
- Regulation of dry air temperature (only in conjunction with optional
optional temperature and air conditioning installed downstream).
- Temperature-dependent residual stroke
- Integrated control cabinet with all necessary devices for operation
in accordance with the TROTEC standard: main on/off switch.
off, selector switch for remote/on-site operation, indicator lights for
signaling lights, keypad, control unit, fuses, wiring and connection terminals
- Casing prepared for reverse mounting. Air direction reversal;
standard process air direction from left to right